Ejector Pump Size Calculator
Find the flow and head your ejector pump must deliver, from the discharge pipe size, the vertical lift and the length of pipe.
Pump duty point
Enter your lift and pipe run, then press Size the pump.
How the size is worked out
The flow comes from the code: a pump on a 2-inch discharge must deliver at least 21 gpm, which keeps the water moving at about 2 feet per second so solids do not settle. The head is the vertical lift plus friction in the pipe, estimated with the Hazen-Williams formula for PVC and about 5 feet of pipe for each elbow or fitting.
Pick a pump whose published curve passes through or above that duty point. A pump far larger than needed short-cycles in a small pit.
Code minimums
- Sump pit at least 18 inches across and 24 inches deep, with a gastight removable cover (IPC 712.3.2).
- Pumps that take toilet waste must pass 2-inch solids.
- Minimum capacity: 21 gpm for a 2-inch discharge, 30 gpm for 2½-inch and 46 gpm for 3-inch (IPC Table 712.4.2).
- A check valve and a full-open valve on the discharge line, and a vented pit.
Your state or city may amend these rules; Los Angeles, for example, uses the Uniform Plumbing Code instead.
Common questions
What size ejector pump do I need for a basement bathroom?
For a 2-inch discharge, at least 21 gpm at your total head. Read the duty point off the maker's pump curve, not the horsepower.
Can I use a sump pump for sewage?
No. A sump pump is not built to pass solids. Toilet waste needs a sewage ejector or grinder in a sealed, vented pit.